How Do Engineers Remove Hundreds of Watts of Heat From a Small Piece of Silicon?
Graphics chips are in the spotlight right now. Behind the headlines sits a quieter engineering challenge: heat. Every watt a chip uses ends up as heat, and engineers must move it out. GPU cooling now spans two very different worlds. One is a gaming card in a home PC. The other is an AI rack drawing more than 100 kilowatts. Both rely on the same physics.
Gaming Cards: From 250 Watts to 575
For about a decade, high-end graphics cards stayed around 250 to 260 watts, according to NVIDIA. Then power jumped to 350 watts in a single generation. Today the GeForce RTX 5090 is rated at 575 watts of total graphics power. Yet NVIDIA’s Founders Edition fits its cooler into just two slots.
The Heat Path
Heat flows through a chain of materials, and each link must conduct well. First, a thermal interface material fills the microscopic gaps between the chip and the cooler. The RTX 5090 Founders Edition uses liquid metal for this job. Next, a vapour chamber spreads the heat across a large plate. That plate sits over the GPU, the memory chips and the power circuitry.
Five copper heat pipes then carry the heat to two fin stacks. Two fans blow air straight through those fins. Heat pipes and vapour chambers work by phase change. A liquid inside evaporates at the hot end, carries heat as vapour, then condenses at the cool end and returns.
Why Air Runs Out in the Data Centre
AI accelerators use far more power per chip. NVIDIA’s A100 drew 400 watts, the H100 drew 700 and the B200 about 1,000. Newer Blackwell Ultra parts are reported near 1.4 kilowatts. Racks multiply that. NVIDIA’s GB200 NVL72 rack holds 72 GPUs and draws roughly 120 to 132 kilowatts.
Traditional air-cooled racks were built for around 8 to 15 kilowatts. At that gap, air simply cannot carry enough heat.
Liquid Takes Over
The GB200 NVL72 ships only as a liquid-cooled rack. Direct-to-chip cold plates sit on the GPUs, CPUs and network switches. Coolant carries the heat to a coolant distribution unit, then out to a facility water loop of roughly 2 litres per second per rack. HPE’s figures put about 115 kilowatts into liquid and 17 into air. A typical sidecar coolant unit handles 60 to 80 kilowatts, so a 130-kilowatt rack needs more.
Other approaches exist. Two-phase cold plates let a refrigerant boil at the chip, which handles higher heat flux. Immersion cooling submerges whole boards in fluid and tends to suit very dense, uniform fleets.
What Engineers Must Get Right
Moving this much heat is a mechanical design problem. Coolant must reach every cold plate evenly across 72 GPUs. Pressure drop must stay low enough for the pumps. Joints must stay leak-tight for years, and materials must tolerate the coolant.
Engineers test and validate all of it. CFD predicts flow and temperature. FEA checks stress and thermal movement. Test rigs then measure real performance.
What This Means for Engineers
GPU cooling shows thermal design moving to the centre of product design. The chip sets the heat, and mechanical engineers decide whether the system can handle it. Our article on CFD analysis services explains how flow and heat transfer are predicted. Our article on test rig design shows how real performance is proven.
At CNR, CFD, thermal analysis, mechanical design and bespoke test engineering work together across aerospace, automotive, defence, energy and research. Whether the heat source is a chip, a motor or a bearing, that experience is where the conversation starts.